Techno-economic Modeling of Stand-Alone Solar Photovoltaic Systems: A case Scenario from South Sudan
Aban AyikI, *; Nelson IjumbaII; Charles KabiriIII; Philippe GoffinIV
IMember, IEEE, African Centre of Excellence in Energy for Sustainable Development, College of Science and Technology, University of Rwanda, KN 73 St, P.O.Box 3900, Kigali, Rwanda (Email: ayik_218014527@stud.ur.ac.rw)
IISenior Member, IEEE, Fellow, SAIEE, African Centre of Excellence in Energy for Sustainable Development, College of Science and Technology, University of Rwanda, KN 73 St, P.O.Box 3900, Kigali, Rwanda, and School of Engineering, University of KwaZulu-Natal, Durban, South Africa (Email: ijumban@ukzn.ac.za)
IIIAfrican Centre of Excellence in Energy for Sustainable Development, College of Science and Technology, University of Rwanda, KN 73 St, P.O.Box 3900, Kigali, Rwanda (Email: c.kabiri@ur.ac.rw)
IVAfrican Centre of Excellence in Energy for Sustainable Development, College of Science and Technology, University of Rwanda, KN 73 St, P.O.Box 3900, Kigali, Rwanda (Email: philippe.goffin@alumni.ethz.ch)
ABSTRACT
South Sudan is expansive and sparsely populated with over 80% of the population living in rural areas. The country has no national grid connecting its cities and towns, thus making rural areas "good candidates" for stand-alone renewable energy systems. This study was conducted to determine the technical feasibility and economic viability of a stand-alone photovoltaic (PV) system compared to a diesel generator. A techno-economic model was developed to forecast the performance of the PV system. The system was initially designed using the IEEE Recommended Practice for Sizing of Stand-Alone Photovoltaic Systems (IEEE P1562-2021) and the IEEE Recommended Practice for Sizing Lead-Acid Batteries for Stand-Alone Photovoltaic Systems (IEEE 1013-2019). The solar radiation data used for modeling were acquired from the Ineichen clear sky model and then transposed to the plane of array irradiation using pvlib python. The system optimization and sensitivity analysis was performed under various diesel fuel costs using the Hybrid Optimization of Multiple Energy Resources (HOMER) software. Results show that at a fuel price of $ 2 per liter, the levelized cost of electricity (LCOE) of the PV system is 64% lower than that of the diesel generator and that the system can earn 11% return on investment (ROI) and recover the investment in about 5.5 years. With a drop in price of diesel fuel to $1 per liter, the payback period increases to about 7 years. These results show that standalone PV systems are technically feasible and economically viable in rural and peri-urban areas of South Sudan.
Index Terms: IEEE Standards, renewable energy, pvlib python, solar photovoltaic, South Sudan, techno-economic modeling
I. INTRODUCTION
"We have entered the decade of renewables!" [1]. In 2019, about 80% of the newly installed global electricity capacity was from renewables, with solar and wind accounting for about 50% of the total capacities [1]. In Africa, the installed renewable electricity capacity has increased in the past decade
by around 93.8%, of which about 20% was from solar generation [1]. Despite the deficit in access to electricity in Sub-Saharan Africa, there has been noticeable progress in the past decade. In 2011, countries such as Rwanda, Tanzania, Ethiopia and Kenya had almost null solar electricity capacity in their generation mix and by 2020, they had installed operating solar power plants with total capacities ranging between 20 MW and 105 MW [1].
South Sudan is an oil-rich country with an area of 619,745 square kilometers (sq. km) and a population density of 13.3 people per sq. km [2]. The country has abundant untapped renewable energy resources (solar, hydropower and wind beside others), which can be exploited to generate electricity. However, despite all available resources, South Sudan remains the "least electrified country in the world". The country replaces Yemen and tops the list of the top 20 electricity access-deficit countries in the world [3]. South Sudan has no national grid connecting its cities and towns and the current available distribution network is about 395 km (145 km medium voltage and 250 km low voltage) in the capital city Juba [4], [5].
A study conducted in 2020 showed that many business owners in Juba city meet their electricity needs by deploying stand-alone diesel generators and solar photovoltaic systems (PV) [6]. Diesel generation alone accounted for about 98% of the total stand-alone generation with monthly fuel costs reaching up to 533,204 United States dollars ($) and carbon dioxide emissions (CO2e) amounting to 1553.8 tons (t) in addition to noise pollution [6]. The study also showed that the use of solar energy for electricity generation among the business owners was very limited (2%), mainly due to the inadequate knowledge about their use.
Currently, South Sudan is planning to improve electricity access through developing renewable energy resources besides investing in transmission infrastructure [7], [8]. However, the construction of transmission and distribution lines all over South Sudan may not be feasible in the "near future" as the country is expansive and sparsely populated, with over 80% of the population living in rural areas [9], [10]. The cost of constructing a transmission network in "rural and peri-rural" areas is usually expensive and exceeds the expected economic and social benefits as some stakeholders may remain unconnected even after several years of constructing the electricity [11], [12]. Therefore, in the absence of "near future" plans to construct a reliable transmission backbone in a country with abundant renewable energy resources, rural and remote communities usually become "better candidates" for standalone renewable energy systems for electricity generation [13]. Stand-alone, or off-grid, renewable energy systems are electrical systems that "operate independently" from the main electricity grid. A few studies have recommended using hybrid and stand-alone renewable energy systems to improve access to electricity in South Sudan [8], [14]. In fact, several solar Photovoltaic (PV) projects have been developed in the country. For example, the development of a microgrid pilot project to power a local market in Northern Bahr el Gazal state (developed by SunGate Solar, a national company) and the installation of a 350 kW solar PV system in the Equatorial Tower in Juba [15].
To correctly forecast the performance of a stand-alone PV system, it is fundamental to first develop an accurate and reliable techno-economic model of the system through simulation and modeling [16]. Several studies have been conducted on the assessment, design and techno-economic modeling of stand-alone solar PV systems using different methodologies [17]-[19]. However, there is very limited literature on the technical and economic analysis of stand-alone solar PV systems in South Sudan. Therefore, it is necessary to assess the technical and economic performance of stand-alone PV systems in South Sudan through modeling and simulation before scaling up their development. The results obtained will enable informed decisions to be made about country-wide deployment of commercial and non-commercial stand-alone PV systems.
This paper is reporting on studies made for developing a techno-economic model for stand-alone PV systems for commercial and community use in populated rural and peri-urban areas of South Sudan. The specific objective was to assess the technical feasibility and economic viability of the PV system compared to diesel fuel-based generation of electricity, to inform decision making in the development of stand-alone solar PV systems in the country.
Stand-alone PV systems mainly consist of solar PV arrays, solar charge controller, solar battery and a DC-AC solar inverter. In the current work, the solar PV array was designed using the methods in the IEEE Recommended Practice for Sizing of Stand-Alone Photovoltaic (PV) Systems (IEEE P1562-2021) [20]. Also, the battery storage system was designed using the IEEE Recommended Practice for Sizing Lead-Acid Batteries for Stand-Alone Photovoltaic (PV) Systems (IEEE 1013-2019) [21]. The PV array was also sized using mathematical modeling with Matlab/Simulink and then the results were compared to check the consistency between the two methods. Subsequently, a financial model was developed using the Hybrid Optimization of Multiple Energy Resources (HOMER) software.
The remainder of this paper is organized as follows:
•Section II elaborates more on the methodology used in this paper to develop the techno-economic model.
•Section III presents and analyzes the results.
•Section IV provides the conclusion to this work and proposes recommendations for future work
II. Methodology
To assess the technical performance of the stand-alone PV system, the size of the system's components had to be determined. Sizing stand-alone PV systems differs from grid-connected systems [22]. Stand-alone PV systems are designed to meet the daily load demand rather than the annual demand [22]. As a result, each component of the PV system must be carefully sized to satisfy that requirement [22], [23]. The PV array must be sized to fully charge the battery bank [22]. Consequently, the capacity of the PV array (number and wattage of PV modules) that can generate the required power to fully charge the battery bank must be determined [23]. The capacity of the PV array is usually influenced by the solar radiation at the study location, the array-to-load ratio (A:L), the daily load, and the system losses [20]. Therefore, site selection, the solar resource at the site, and the estimate of the average daily load must be carefully considered in the design to avoid over-sizing or under-sizing the stand-alone system. Similarly, the battery bank size that can continuously supply electrical power to the load, at night or during periods of low solar radiation, must be precisely calculated [22]. So, the battery bank size is determined by the average daily load besides the battery type and parameters [24].
In off-grid systems, inverters are needed to convert the battery DC voltage into AC and it is necessary that the voltage input into the selected inverter matches the system voltage [23]. Inverters may vary in size according to their capacity, power quality, and output voltage [25]. Charge controllers are also important components of the stand-alone system that protect the storage battery from over-charging or over-discharging. Also the charge controller can be integrated with a maximum power point tracker (MPPT), a "DC-to-DC converter", to increase the energy generated by the PV modules [25].
Once the size of the stand-alone PV system components are determined, its technical performance, in terms of output power and energy yield, can be calculated. The financial performance can then be evaluated by using different economic metrics.
The following sections describe the steps and techniques which were used to evaluate the technical and financial performance of the stand-alone PV system.
A. Study location
The preliminary step in the design of the PV system was to identify a suitable location with adequate solar resource. Long-term daily average global horizontal irradiation (GHI) data of South Sudan were downloaded from the Global Solar Atlas to search and locate areas of high solar resource potential in the country. Gok-Machar town market (latitude 9.21850, longitude 26.86787), in the north western part of South Sudan, was selected for the case scenario based on the high solar resource in that location (Fig.1) besides the potential for agribusiness activities and other related businesses.
Gok-Machar is a town in Aweil North county of Northern Bahr el Ghazal state. About 80% of households in Aweil North county depend on farming and agricultural activities for their livelihoods besides undertaking other small-scale business activities [26]. Gok-Machar is located in an area with a daily average GHI on a horizontal plane ranging between 5.9 and 6.3 kWh/m2 (based on the data from the Global Solar Atlas) . Similar to many other towns in South Sudan, Gok-Machar has no access to grid electricity, so businesses there depend on diesel generators and small-scale solar PV systems for their electricity needs.
As of December 2022, one liter of diesel fuel in the parallel market in Gok-Machar was 1400 South Sudanese pounds, which was equivalent to $ 2 [27]. In November 2022, diesel fuel price in the capital city Juba was equivalent to $ 1.32 per liter and the cost of 1 kWh of utility electricity was equivalent to $ 0.334 (calculated from actual monthly residential electricity consumption).
B. Load profile
The main purpose of installing the PV system in the current scenario was to provide electricity to commercial customers in Gok-Machar market. The system was also expected to provide electricity to a few nearby domestic customers. Therefore, 300 commercial and domestic customers were expected to benefit from the solar PV system. The customers were divided into four categories:
•Category one consisted of 82 households (5% high-income, 45% middle-income and 50% low-income).
•Category two consisted of 200 businesses (retail and wholesale shops, motels, groceries, internet cafes, butcheries, restaurants, hair salons, farms and other small businesses).
•Category three consisted of eight public facilities (two schools, three offices, one guest house, one hospital and one community center).
• Category four consisted of 10 private facilities (four offices, two schools, two churches, one mosque and one medical complex).
Table I shows the list of the appliances powered by the solar PV system. The power rating of each appliance is commonly found on the appliance (nameplate or stamp). The total daily load consumption (all appliances) was calculated, using Excel, as shown in the following steps:
• The total daily energy consumption of each individual load (in Wh) was calculated by multiplying the power rating of the appliance (in W) by its daily operational duration (in hrs) and by the total available quantity.
• The daily energy consumed by all loads were then added up to obtain the total daily load consumption (in Wh).
The daily load profile, showing the distribution of the load over the 24 hrs, was developed, as shown in Fig. 2.
C.System voltage
The total daily load and energy consumption were estimated as 100 kW and 560 kWh respectively. The system voltage was selected based on the daily load consumption. It is recommended to use 12 V for systems with loads less than 1 kWh, 24 V for loads between 1 kWh and 4 kWh and 48 V for loads above 4 kWh a day [13]. Therefore, the nominal voltage of the system in the current study was chosen as 48 V.
D.Sizing of the battery storage system
The solar storage battery is one the most expensive parts in an off-grid PV system [28], [29]. When selecting battery types, some important factors to take into consideration include the effect of overcharging and high temperatures on the characteristics of the battery, maintenance and performance at deep cycle [23]. Two commonly used batteries for energy storage in off-grid PV systems are lead acid and lithium ion (Li-ion) batteries [30]. Lead acid batteries are "the oldest and most widely" used worldwide, commonly and widely available in various sizes, low cost, 100% recyclable, durable, reliable and easy to manufacture [31]-[33]. The main drawbacks of lead acid batteries are short cycle life, low energy density, less efficiency in cold temperatures and fast discharging at high temperatures that affects their lifetime [29], [30]. On the other hand, Li-ion batteries are "relatively new" compared to lead acid batteries. They mainly have long cycle life, high energy density, high charging and discharging capability; and are maintenance free [31]. However, Li-ion batteries have safety concerns due to thermal runaway and overcharging, besides the decrease in performance due to "high temperature and high voltage" [30], [31]. Li-ion batteries are also difficult to dispose of and recycle compared to lead-acid batteries [34]. More information about the advantages, disadvantages, and hazards of deep cycle batteries used in off-grid systems can be found in references [23] and [31].
Lead-acid batteries were used in the current study because they are commonly used in off-grid systems especially in rural areas. Therefore, the solar battery was designed according to the IEEE 1013-2019 recommended practice for sizing lead-acid batteries [21]. The IEEE 1013-2019 is used for sizing flooded and valve-regulated (VRLA) lead-acid batteries for residential and commercial and industrial stand-alone PV systems [21]. The information required to appropriately size the solar battery included the following:
•Total daily load in Ah
•Required days of autonomy
•Depth of discharge (DOD)
•Maximum current withdrawn by the load
•Maximum and minimum battery voltage
At this stage, the selection of a "trial battery type" was necessary to determine the design DOD and maximum and minimum battery voltage. The 2 V OPzS type battery was initially selected as a "trial battery". The OPzS (Ortsfest Panzerplatte Flüssig in German) is a robust, low-maintenance flooded lead-acid battery that is commonly used in stationary off-grid applications. The lifetime of the OPzS battery can exceed 15 years if operated between 20°C to 25°C and 50% depth of discharge (DOD). The sizing method is summarized by the steps presented in Fig. 3.
E. The solar resource at the study location
The PV modules were sized using the IEEE P1562-2021.
The IEEE P1562-2021 uses the "Peak Sun-Hour" method to size the solar PV modules [20]. The peak sun-hours (Sh) is defined as the time, in hours, needed to produce average daily solar irradiation in kWh/m2 when the solar irradiance is 1 kW/m2 [13], [20]. In this method, the PV system sizing is based on the "worst-case" monthly solar irradiation, energy consumed and system losses [20]. Solar PV modules are usually rated at standard test conditions (STC) that are equivalent to an irradiance of 1 kW/m2, cell temperature of 25 °C and Air Mass of 1.5 [13]. However, the actual power produced by a PV module can vary depending on the irradiation and the ambient operating temperature [20]. Therefore, to estimate the actual power output from a PV module, it is necessary to calculate the sun-hours from the solar radiation incident on the modules at the optimum tilt and azimuth.
In this study, the solar radiation incident on the tilted PV module, also known as the plane of array (POA) radiation, was calculated from the radiation in the horizontal plane using pvlib python. Pvlib python is an open source software used for modeling and simulating solar energy systems [35], [36]. Solar PV modules are usually inclined at an angle equal to the latitude and directed north if in the southern hemisphere or south if in the northern hemisphere. However, this can be different at locations between latitudes 0° to 15° from the equator [20]. Therefore, the PV modules were modeled at various tilt angles and orientations to get the optimal solar irradiation at each location.
A time series of 16 years (2005 to 2020) of hourly global horizontal irradiance (GHI), direct normal irradiance (DNI) and diffuse horizontal irradiance (DHI) for the study location was acquired from the Ineichen clear sky model through pvlib python. The Ineichen model is one of the "most accurate" clear sky models for global horizontal irradiance (GHI), which is simple to use as it does not require site specific data apart from the geographic location (latitude and longitude) [37]. The irradiance data were then transposed to POA using the Hay/Davies transposition model. Transposition models calculate the POA irradiance by estimating the direct irradiance, ground diffuse and sky diffuse components [19].
To get the maximum monthly ambient temperature at the study location, daily maximum temperatures (from January 2005 to December 2020) were downloaded from NASA's Prediction of Worldwide Energy Resource (POWER) [38]. The long-term monthly average temperatures were calculated and the value for the month with the maximum temperature was selected.
F. Sizing of the PV module using IEEE P1562-2021
The IEEE P1562-2021 calculated the voltage of the PV module at a temperature different from the standard temperature (i.e. 25 °C) using the following equation:
where, Vm_new is the maximum power point voltage at the operating temperature, Vm is the maximum power point voltage at STC, Tn is the module maximum operating temperature at standard operating conditions (SOC) in °C, and kv is the open circuit voltage temperature coefficient in V/°C. If kv is given in %/°C then it must be converted to V/°C first before substituting in (1).
Similarly, the maximum power point current (Im_new) and power (Pm_new ) at the operating temperature were calculated by replacing Vm in (1) with the maximum power point current (Im) or power (Pm) at STC using similar equations when the short circuit current (ki) and maximum output power temperature coefficients (kp) are given. The temperature, Tn, at SOC was estimated using by the following expression [13]:
where Ta is the ambient operating temperature. The nominal operating cell temperature (NOCT) is usually given in the PV module manufacturer's data sheet.
For a system with an MPPT, the minimum number of series connected PV modules are estimated using the following expression [20]:
where Nseries is the minimum number of series connected PV modules, Vmax is the absorption battery voltage, and Vlosses are voltage losses (assumed 0 because voltage losses are included in system losses).
The number of parallel connected PV modules, Nparallel, of the PV modules were calculated using the following expression [20]:
where LDW is the average daily load in watt hours (Wh), A:L is the array to load ratio, σL is the system losses, Sh is the sun hours, and ηis the MPPT charge controller efficiency. Results from (3) and (4) were rounded up to the nearest whole number.
The technical specifications of the selected PV module for this case scenario are presented in Table II, where Isc and Voc are the PV cell short-circuit current and open-circuit voltage respectively.
The following assumptions were considered for the PV system design:
•The daily load was constant throughout the month for all months.
•No shading of the PV array throughout the day.
•System losses are 30% (typical system losses are 10% to 35%) [20].
G.Sizing of the PV module using MATLAB/Simulink
One of the most widely used methods for the design of solar PV systems is mathematical modeling using Matlab/Simulink [39]-[41]. To validate the results obtained using the IEEE P1562-2021, the PV modules were also designed using the equations of the single diode circuit of a solar PV cell using Matlab/Simulink. The hourly current from a solar PV module can be expressed by the following equation [42]:
where, I is the hourly output current of the PV module in ampere, Ns the number of PV cells connected in series, Iph the hourly generated current of solar modules in ampere (photo-current), IO the hourly saturation current in ampere, q the charge of the electron in Coulombs, 1.6 × 10-19 C, V the hourly output voltage in volts, Rs the series resistance in ohm, n the ideality factor for the p-n junction, K the Boltzmann's constant in Joules per Kelvin, 1.38 × 10-23 J/k, T the operating cell temperature in Kelvin, Ish the current through the shunt resistor in ampere, and Rsh the shunt resistance in ohm.
The series and shunt resistors (Rs and Rsh) and the ideality factor (n) were estimated using iterations starting with an initial value of Rs equals 0 [43]. Also the ideality factor (n) was chosen arbitrarily depending on the parameters of the model [43].
The detailed equations of the photo current (Iph) and saturation current (IO) can be found in references [25], [29] and [43]. The output from the Simulink model were then compared with the output from the IEEE P1562-2021 method.
H.Sizing of the charge controller
In this study, the MPPT charge controller was used to regulate the "charging and discharging" of the PV system storage battery. one of the merits of the MPPT charge controller is that it can handle PV modules at a higher voltage and then match the output voltage with the voltage of the battery. The MPPT charge controller was sized, based on the PV module open circuit voltage,Voc, using the following equations [44]:
where Nstrings is the maximum number of PV modules that can be connected (in series) to the charge controller, 0.95 a safety factor, and Vmppt the charge controller maximum input voltage.
I. Sizing ofthe inverter
In South Sudan, the standard voltage required by electrical appliances and equipment is 230 V for single-phase connection and 400 V for three-phase at a frequency of 50 Hz. Therefore, an inverter was necessary to convert the battery DC voltage into AC. Inverters are normally listed by their "capacity in watts or kilowatts and output voltage" [25]. When sizing the solar inverter, it was necessary to ensure that the input power into the inverter exceeded the total power needed by the AC load [23]. The minimum inverter input power, Pi_min, was calculated using the following expression [23]:
where 1.25 is a safety factor. Current for momentary (surge) loads were estimated as seven times the running current.
Table III presents technical data and information on the selected MPPT charge controller and inverter.
J. Building a financial model using HOMER
The Hybrid Optimization of Multiple Energy Resources software (HOMER Pro) was used for the optimum design and economic modeling of the PV system. HOMER Pro is a powerful software used in the techno-economic design of stand-alone off-grid and grid-connected renewable energy systems [45]-[49]. The input and output data to HOMER are shown in Fig 4.
HOMER selects the best system by optimizing the model and through sensitivity analysis and then estimates the system's total net present value of costs (NPC), initial capital, operation and maintenance costs (O&M), levelized cost of electricity (LCOE) and other economic metrics. HOMER ranks system configuration based on the NPC. The NPC involves the conversion of all costs occurring in the future to their present equivalent and combining them with the initial investment cost to get the total value of the costs of the project [50]. Therefore, the project with the lowest NPC is the most preferred [50]. The NPC can be expressed by the following [50]:
where, N is Project lifetime in years, Ct is the costs in year t ($), i is the discount rate (%), and IO is the initial investment ($).
Although HOMER does not rank systems based on the LCOE, the LCOE can be useful when comparing two or more systems. The LCOE is the break-even price needed to recover the initial investment and it is defined as the NPC divided by the present value of costs of energy produced by the system [51], [52]. LCOE can be expressed mathematically by the following expression [51], [52]:
where, Et is the energy production in year t (kWh).
Other important economic metrics calculated by HOMER included Return on Investment (ROI) and Discounted Payback Period (DPP). ROI is defined as "the net profit per year as a ratio of initial investment" [50]. ROI is expressed as a percentage and is an indicator of the profitability of a project. The DPP is the time required to recover an investment after which the project starts generating profits [53]. The DPP is a convenient way to assess investments especially in risky environments as the shorter the DPP, the better the investment as profits can be recovered faster.
Cost information input into HOMER are shown in Table IV. Initial capital included purchasing, transport and installation costs. HOMER modeled the MPPT charge controller together with the PV module. Sensitivity variables were diesel fuel price and battery lifetime.
III. RESULTS AND DISCUSSION
A. Battery bank size
The results obtained from sizing the solar battery system using IEEE 1013-2019 are shown in Table V.
Based on the obtained results, the solar system battery bank consisted of 46 parallel strings. However, the practical cell capacity available of the selected type at the functional-hour rate was 8430 Ah (that is 2810 Ah x 3 strings in parallel), which meant that the parallel strings must be a number divisible by 3 (45 or 48 parallel strings instead of 46). For cost effectiveness, the battery size was selected as 45 parallel strings of 24 batteries each. Therefore, the final battery capacity became 126450 Ah, rated at the 172 h functional-hour rate (15 banks, each with 3 strings of 24 batteries) and the battery's capacity for each day of autonomy will be 25290 Ah (3 banks, each with 3 strings of 24 batteries).
B. The POA irradiation
The solar resource in Gok-Machar was modeled at tilt angles ranging between 8° and 25° with south, southeast, south-west, north, east and west orientations using pvlib python. To identify the optimum tilt and orientation, long term monthly and annual averages and sums of POA irradiation values with percentage transposition gain, were compared at each tilt and orientation, as shown in Fig. 5 and Fig. 6.
Results show that the highest monthly transposition gain obtained was 22.4% with a tilt angle of 25° south. However, the highest drop in POA irradiation (up to 23.2%) was also found at the same tilt and orientation. The southwest facing PV modules produced the best results in terms of monthly, annual and percentage gain in POA irradiation, followed by the south and west facing modules, respectively. Results also show that the best monthly average POA irradiation was produced with tilt angles between 10° and 13° southwest and that the optimum tilt and orientation was 13° southwest. It was also observed that as the tilt angle increased beyond 13°, the drop in irradiation increased with all orientations.
The month with the lowest POA irradiation at the optimum tilt and orientation was June and it had a GHI of 6.54 kWh/m2. That value was converted to 6.54 sun hours for PV design calculations using the IEEE P1562-2021 method. Also, the maximum ambient average temperature at the study location was observed in March and it reached 40.72 °C.
C. The calculated size of the PV array
The P-V and I-V curves of the PV module, produced using Simulink at different operating temperatures, are shown in Fig. 7. Using iterations, the values of Rs, Rsh and n were estimated as 0.237, 460.28 and 1.086 respectively.
The calculated PV array size, using IEEE P1562-2021 and Simulink are shown in Table VI. Examining the results obtained, it is observed that the PV array sizing using the IEEE P1562-202 method yielded the same results as the sizing using Simulink. This showed that the IEEE P1562-202 recommended method is a reliable method for sizing PV arrays in a PV system. The "IEEE PES 1013 and 1562 standalone solar system battery and array sizing Calculator" presents a simple and efficient way to implement both the IEEE P1562-202 and IEEE 1013-2019 methods [54].
D. Calculated size of the MPPT charge controller
• Nstrings = 10
•Selected number of series connected modules = 9
•Number of parallel connected PV strings/ MPPT = 2
•Total number of MPPT charge controllers = 31
•Final number of PV modules = 558
•Final PV system output power = 168.20 kW
E.Calculated size of the inverter
•Inverter output power = 50.4 kW
•Number of inverters = 8
F.HOMER simulation results
The best possible size of the PV system components were determined using the HOMER optimizer. The battery storage was sized using search space values of 0, 3, 6, 9, 12, 36, 39, 42, 45, and 48 strings (values divisible by 3). The selected sensitivity variables were diesel fuel prices of $ 1.0, and $ 2.0 per liter, and battery lifetime of 6 and 10 years.
Table VII shows the results of the simulation and optimization performed by HOMER. HOMER ranked PV system no.1 as the best (winning system) because it had the lowest NPC compared to the other simulated systems. System no. 1 earned 78.5% ROI and recovered the investment in about 15 months, when diesel fuel prices were at their lowest (i.e. $ 1/liter). Also, the ROI and DPP of system no. 1 were not affected by the decrease in battery lifetime. However, system no. 1 had 26.2 hrs of autonomy (about 1 day and 2 hours) due to its designed storage capacity. In stand-alone off-grid PV systems, the battery storage is designed to assist the electrical load during periods of low solar irradiation. Hence, the battery is a critical part of the stand-alone system and any trade-off between reliability and cost may compromise the reliability of the entire system. That's why the IEEE P1562-202 recommends a minimum of five days of autonomy (120 hrs) for stand-alone PV systems in areas of high solar potential to ensure system reliability and availability. Therefore, system no. 2, which was ranked by HOMER as the best system with 122 hrs of autonomy, was selected as the winning system in this study.
At the current diesel fuel price of $ 2/liter in Gok-Machar and with battery lifetime of 10 years, the PV system no. 2 can sell a kWh of electricity for $ 1.08 (nearly 62% lower than the price of electricity generated by the diesel generator), earn 11% ROI and recover the investment in 5.5 years. With a drop in price of diesel fuel to $1 per liter, the PV system can still recover the investment in about 7 years and earn a reasonable 6.6% ROI.
The battery bank is one of the most expensive components of the PV system. If battery lifetime is reduced to 6 years with diesel fuel price of $ 2/liter, the PV system can recover the investment in about 10 years. However, if fuel prices drop to the current price in Juba or less, then the PV system will not be able to payback the invested capital until the end of its lifetime. Hence, the system will not be economically viable compared to a diesel generator. This shows that the decrease in the lifetime of the storage system has a great impact on the the economic viability of a standalone PV system as replacement costs increase. To increase the lifetime of a lead-acid battery in environments with elevated temperatures, it is recommended to install and operate the batteries in ambient temperatures ranging between 20°C and 25°C [55]. This can be achieved by using "well-designed" ventilation and air conditioning systems [55]. However, ventilation fans and air-conditioning systems will need extra energy from the PV system. This makes economically viable systems with excess energy (about 4.78% excess energy), such as PV system no. 3, preferable. The LCOE of system no. 3 is the same as system No. 2 but the NPC of system no. 3 is higher by 0.003% compared to the NPC of system no. 2, making the difference between the two negligible.
Although the LCOE of system no. 2 was lower than the LCOE of the diesel generator, it was still high compared to system no. 1 and to the utility electricity price in Juba. The LCOE can be lowered by reducing the maintenance and operation expense of the system (cleaning and maintaining the PV arrays, battery storage and inverter) and the replacement cost of the storage batteries. Cleaning of the PV arrays and the surface of the storage battery bank can be performed by trained community volunteers. The replacement expense of the battery can be reduced by extending the battery life. Lead acid batteries are about 99% recyclable and part of their cost can be recovered through recycling.
These results show that stand-alone PV systems are technically feasible and economically viable for commercial and community use in populated rural and peri-urban areas of South Sudan. Therefore, authorities should encourage investment in such systems by adapting favorable policies and regulations for the installation of sustainable energy systems (long term contracts, capital subsidies beside others). This will attract and encourage local and international investors to develop commercial and community stand-alone PV systems and other renewable energy systems in the country.
Investment in renewable energy projects in countries like South Sudan may come with risks due to various factors (economic, environmental, social beside others). Consequently, investors may favor investment in systems similar to system no.1 to secure shorter payback periods and higher ROIs. However, it is important to note that when designing and developing electrical systems, it is crucial to adhere to national and international standards, regulations and recommendations. This will ensure system safety, optimal design and performance, quality and reliability.
G. Comparison of study results with the literature
The results of the current study were compared with results obtained from similar case studies within the region as shown in Table VIII. Considering the viability of off-grid solar PV systems for domestic and commercial use in remote, rural, and peri-urban areas across Africa, the findings of these studies showed agreement with the findings of the current study.
IV. Conclusion
The main purpose of this study was to assess the technical feasibility and economic viability of a stand-alone solar photovoltaic (PV) system and compare it to a diesel generator in densely populated rural and peri-urban areas of South Sudan. Gok-Machar, a town in Aweil North county of Northern Bahr el Ghazal, was selected as the study case scenario. To correctly forecast the performance of the PV system, a techno-economic model was developed through simulation and modeling. The PV arrays were sized using the IEEE Recommended Practice for Sizing of Stand-Alone Photovoltaic Systems (IEEE P1562-2021). The IEEE P1562-2021 was validated using Matlab/Simulink. The battery storage was also sized using the IEEE Recommended Practice for Sizing Lead-Acid Batteries for Stand-Alone Photovoltaic Systems (IEEE 1013-2019). Then, the PV system optimization and financial modeling was performed using the Hybrid Optimization of Multiple Energy Resources (HOMER) software.
Results show that at the current diesel fuel price in Gok-Machar, the PV system can sell 1 kWh of electricity at a price 62% lower than the price of the electricity generated by the diesel generator. The system can then earn 11% return on investment (ROI) and recover the investment in about 5.5 years. Even when one liter of diesel fuel drops to $ 1 in Gok-Machar, the PV system can still earn 6.6% return and recover the funds invested in 7 years, after which it will generate profits until the project ends. The study concluded that, standalone PV systems are technically feasible and economically viable in densely populated rural and peri-urban areas of South Sudan. Results from this research were compared with other similar studies from the region and the findings were found in agreement with the current study. This shows that this research has broader implications beyond South Sudan. The outcome of the study is indeed of benefit to the research community specifically, countries in the region and developing countries with similar challenges.
The following are recommendation to consider for further future studies:
•Techno-economic modeling of stand-alone PV systems in rural and peri-urban areas of low solar resources.
•Techno-economic modeling of direct-coupled (DC) standalone PV systems.
•The economics of Lithium-ion and salt-water batteries in stand-alone PV systems including recycling and disposal costs.
•Study the cost of recycling and disposal of the PV arrays at the end of the project life.
Acknowledgments
The authors would like to thank the African Centre of Excellence in Energy for Sustainable Development (ACEESD) at the University of Rwanda for funding this study.
References
[1] International Renewable Energy Agency (IRENA), "Renewable capacity statistics 2021," tech. rep., Abu Dhabi, 2021.
[2] The East African Community, "The Republic of South Sudan," 2018.
[3] IEA, IRENA, UNSD, World Bank, and WHO, "Tracking SDG 7: The Energy Progress Report," tech. rep., World Bank, Washington DC, 2021.
[4] African Development Fund, "Juba Power Distribution System Rehabilitation and Expansion Project," tech. rep., African Development Bank, 2013.
[5] M. Galucci, "South Sudan Is Building Its Electric Grid Virtually From Scratch," IEEE Spectrum, 2020.
[6] L. D. M. Lemi and M. C. L. Belle, "Co-supplying the national grid: An assessment of private off-grid electricity generation in juba-south sudan," American Journal of Electrical Power and Energy Systems, vol. 9, no. 3, pp. 47-59, 2020. doi:10.11648/j.epes.20200903.12. [ Links ]
[7] South Sudan Ministry of Finance and Planning, "Republic of South Sudan Revised National Development Strategy (2021 - 2024)," 2021.
[8] N. S. D. Ladu, R. Samikannu, K. G. Gebreslassie, M. Sankoh, L. E. R. Hakim, A. Badawi, and T. P. B. Latio, "Feasibility study of a standalone hybrid energy system to supply electricity to a rural community in south sudan," Scientific African, vol. 16, p. e01157, 2022. doi:10.1016/j.sciaf.2022.e01157. [ Links ]
[9] Ministry of Electricity and Dams (South Sudan) & United Nations Development Programme (UNDP), "The Republic of South Sudan Sustainable Energy for All Rapid Situation Assessment and Gap Analysis Report," Tech. Rep. July, 2013.
[10] South Sudan National Bureau of Statistics (NBS), "National Baseline Household Survey 2009 Report for South Sudan," tech. rep., 2012.
[11] K. Bos, D. Chaplin, and A. Mamun, "Benefits and challenges of expanding grid electricity in africa: A review of rigorous evidence on household impacts in developing countries," Energy for Sustainable Development, vol. 44, pp. 64-77, 2018. doi: 10.1016/j.esd.2018.02.007. [ Links ]
[12] A. H. Hubble and T. S. Ustun, "Scaling renewable energy based microgrids in underserved communities: Latin America, South Asia, and Sub-Saharan Africa," in 2016 IEEE PES PowerAfrica, pp. 134-138, IEEE, Jun 2016.
[13] H. Louie, Off-Grid Electrical Systems in Developing Countries. Cham: Springer International Publishing, 2018. [ Links ]
[14] A. Ayik, N. Ijumba, C. Kabiri, and P. Goffin, "Selection of Off-Grid Renewable Energy Systems Using Analytic Hierarchy Process: Case of South Sudan," in 2020 IEEE PES/IAS PowerAfrica, (Nairobi, Kenya), pp. 1-5, 2020. doi: 10.1109/PowerAfrica49420.2020.9219858.
[15] SunGate, "Wanyjok Micro-grid Project - Sungate Solar," 2022.
[16] K. Raiambal and C. Chellamuthu, "Modeling and simulation of grid connected wind electric generating system," in IEEE Region 10 Annual International Conference, Proceedings/TENCON, vol. 3, pp. 1847-1852, 2002.
[17] M. Kolhe, "Techno-economic optimum sizing of a stand-alone solar photovoltaic system," IEEE Transactions on Energy Conversion, vol. 24, no. 2, pp. 511-519, 2009. [ Links ]
[18] T. Khatib, I. A. Ibrahim, and A. Mohamed, "A review on sizing methodologies of photovoltaic array and storage battery in a standalone photovoltaic system," Energy Conversion and Management, vol. 120, pp. 430-448, Jul 2016. doi: 10.1016/j.enconman.2016.05.011. [ Links ]
[19] M. Lave, W. Hayes, A. Pohl, and C. W. Hansen, "Evaluation of global horizontal irradiance to plane-of-array irradiance models at locations across the United States," IEEE Journal of Photovoltaics, vol. 5, no. 2, pp. 597-606, 2015. [ Links ]
[20] "IEEE Recommended Practice for Sizing Stand-Alone Photovoltaic (PV) Systems," in IEEE Std 1562-2021 (Revision of IEEE Std 1562-2007), pp. 1-35, 2021. doi: 10.1109/IEEESTD.2021.9528316.
[21] "IEEE Recommended Practice for Sizing Lead-Acid Batteries for Stand-Alone Photovoltaic (PV) Systems," in IEEE std 1013-2019 (Revision of IEEE std 1013-2007), pp. 1-50. doi: 10.1109/IEEESTD.2019.8845030.
[22] W. Ali, H. Farooq, A. U. Rehman, Q. Awais, M. Jamil, and A. Noman, "Design considerations of stand-alone solar photovoltaic systems," in 2018 International Conference on Computing, Electronic and Electrical Engineering, ICE Cube 2018, pp. 1-6, IEEE, 2019.
[23] S. Qazi, Standalone Photovoltaic (PV) Systems for Disaster Reliefand Remote Areas. Elsevier, 2017.
[24] "IEEE Guide for Selecting, Charging, Testing, and Evaluating Lead-Acid Batteries Used in Stand-Alone Photovoltaic (PV) Systems," in IEEE Std 1361-2014 (Revision of IEEE Std 1361-2003), pp. 1-39, 2014. doi: 10.1109/IEEESTD.2014.6837414.
[25] N. Kaushika, A. Mishra, and A. K. Rai, Solar Photovoltaics. Cham: Springer International Publishing, 2018.
[26] FAO and WFP, "Special Report - 2021 FAO/WFP Crop and Food Security Assessment Mission (CFSAM) to South Sudan," tech. rep., Rome, June 2022.
[27] World Food Programme, "Economic: Prices - Dataviz - WFP - VAM," 2022.
[28] K. H. Ibrahim, A. Y. Hassan, A. S. AbdElrazek, and S. M. Saleh, "Economic analysis of stand-alone PV-battery system based on new power assessment configuration in Siwa Oasis - Egypt," Alexandria Engineering Journal, vol. 62, pp. 181-191, 2023.
[29] S. Sumathi, L. Ashok Kumar, and P. Surekha, Solar PV and Wind Energy Conversion Systems. Green Energy and Technology, Cham: Springer International Publishing, 2015. [ Links ]
[30] R. Satpathy and V. Pamuru, "Off-grid solar photovoltaic systems," in Solar PV Power, pp. 267-315, Elsevier, 2021.
[31] T. M. Letcher, ed., Storing Energy. Elsevier, second ed., 2022.
[32] K. Varshney, P. K. Varshney, K. Gautam, M. Tanwar, and M. Chaudhary, "Current trends and future perspectives in the recycling of spent lead acid batteries in India," in Materials Today: Proceedings, vol. 26, pp. 592-602, Elsevier Ltd., 2019.
[33] A. Evans, V. Strezov, and T. J. Evans, "Energy Storage Technologies," in Reference Module in Earth Systems and Environmental Sciences, Elsevier, 2022.
[34] B. Huang, Z. Pan, X. Su, and L. An, "Recycling of lithium-ion batteries: Recent advances and perspectives," Journal of Power Sources, vol. 399, pp. 274-286, 2018. doi: 10.1016/j.jpowsour.2018.07.116. [ Links ]
[35] W. F. Holmgren, C. W. Hansen, and M. A. Mikofski, "pvlib python: a python package for modeling solar energy systems," Journal of Open Source Software, vol. 3, p. 884, Sep 2018. [ Links ]
[36] T. Gurupira and A. J. Rix, "Photovoltaic System Modelling using PVLib-Python," Fourth South African Solar Energy Conference SASEC, Stellenbosch, South Africa, vol. 2, no. 1, pp. 1-10, 2016. [ Links ]
[37] J. S. Stein, C. W. Hansen, and M. J. Reno, "Global horizontal irradiance clear sky models : implementation and analysis.," Mar 2012.
[38] Resources NASA Prediction of Worldwide Energy, "POWER Data Access Viewer," 2018.
[39] X. H. Nguyen and M. P. Nguyen, "Mathematical modeling of photovoltaic cell/module/arrays with tags in Matlab/Simulink," Environmental Systems Research, vol. 4, no. 1, 2015. [ Links ]
[40] S. Bana and R. Saini, "A mathematical modeling framework to evaluate the performance of single diode and double diode based SPV systems," Energy Reports, vol. 2, pp. 171-187, Nov 2016. [ Links ]
[41] S. Said, A. Massoud, M. Benammar, and S. Ahmed, "A Matlab/Simulink-Based Photovoltaic Array Model Employing SimPowerSystems Toolbox," Journal of Energy and Power Engineering, vol. 6, no. January 2016, pp. 1965-1975, 2012. [ Links ]
[42] H. M. Ridha, C. Gomes, H. Hazim, and M. Ahmadipour, "Sizing and implementing off-grid stand-alone photovoltaic/battery systems based on multi-objective optimization and techno-economic (MADE) analysis," Energy, vol. 207, p. 118163, 2020. [ Links ]
[43] M. G. Villalva, J. R. Gazoli, and E. R. Filho, "Comprehensive approach to modeling and simulation of photovoltaic arrays," IEEE Transactions on Power Electronics, vol. 24, no. 5, pp. 1198-1208, 2009. [ Links ]
[44] N. I. Abdul Aziz, S. I. Sulaiman, S. Shaari, I. Musirin, and K. Sopian, "Optimal sizing of stand-alone photovoltaic system by minimizing the loss of power supply probability," Solar Energy, vol. 150, pp. 220-228, 2017. [ Links ]
[45] "HOMER - Hybrid Renewable and Distributed Generation System Design Software," 2021.
[46] B. P. P. Tchintchui and A. K. Raji, "Techno-economic analysis of a renewable energy solution for an off-grid residence," in 2019 International Conference on the Domestic Use ofEnergy (DUE), (Wellington, South Africa), pp. 43-50, 2019.
[47] M. Raihan Uddin, S. Mahmud, S. Salehin, M. Abdul Aziz Bhuiyan, F. Riaz, A. Modi, and C. A. Salman, "Energy analysis of a solar driven vaccine refrigerator using environment-friendly refrigerants for off-grid locations," Energy Conversion and Management: X, vol. 11, pp. 43-50, 2021. [ Links ]
[48] G. Ali, H. H. Aly, and T. Little, "Using HOMER software to investigate, size and apply renewable energy sources in a convention center in Sabratha, Libya," in 2021 International Conference on Electrical, Communication, and Computer Engineering (ICECCE), (Kuala Lumpur, Malaysia), pp. 1-6, 2021.
[49] S. O. Fadlallah and D. E. Benhadji Serradj, "Determination of the optimal solar photovoltaic (PV) system for Sudan," Solar Energy, vol. 208, pp. 800-813, June 2020. [ Links ]
[50] S. C. Bhattacharyya, Energy Economics, vol. 297. London: Springer London, 2011. [ Links ]
[51] P. Zweifel, A. Praktiknjo, and G. Erdmann, Energy Economics. Springer Texts in Business and Economics, Berlin, Heidelberg: Springer Berlin Heidelberg, Aug 2017. [ Links ]
[52] C. S. Lai and M. D. McCulloch, "Levelized cost of electricity for solar photovoltaic and electrical energy storage," Applied Energy, vol. 190, pp. 191-203, Mar 2017. [ Links ]
[53] S. B. Bhandari, "Discounted Payback Period-Some Extensions," Proceedings of ASBBS, vol. 16, no. 1, p. 11, 2009. [ Links ]
[54] 1013 and 1562 working groups, "IEEE PES 1013 and 1562 standalone solar system battery and array sizing Calculator," 2022.
[55] "IEEE/ASHRAE Guide for the Ventilation and Thermal Management of Batteries for Stationary Applications," in IEEE Std 1635-2022/ASHRAE Guideline 21-2022 (Revision of IEEE Std 1635-2018/ ASHRAE Guideline 21-2018), pp. 1-140, 30 Nov. 2022.
[56] O. C. Akinsipe, D. Moya, and P. Kaparaju, "Design and economic analysis of off-grid solar PV system in Jos-Nigeria," Journal of Cleaner Production, vol. 287, p. 125055, 2021. [ Links ]
[57] R. Cartland, A. M. Sendegeya, and J. de Dieu Khan Hakizimana, "Socio-economic analysis of solar photovoltaic-based mini-grids in rural communities: A Ugandan case study," Journal ofEnergy in Southern Africa, vol. 33, no. 3, pp. 36-50, 2022. [ Links ]
[58] A. I. Hassane, D. H. Didane, A. M. Tahir, J. M. Hauglustaine, B. Manshoor, M. F. M. Batcha, J. G. Tamba, and R. M. Mouangue, "Techno-economic feasibility of a remote PV mini-grid electrification system for five localities in Chad," International Journal of Sustainable Engineering, vol. 15, no. 1, pp. 179-193, 2022. [ Links ]
[59] M. W. Ijeoma, H. Chen, M. Carbajales-Dale, and R. O. Yakubu, "Techno-Economic Assessment of the Viability of Commercial Solar PV System in Port Harcourt, Rivers State, Nigeria," Energies, vol. 16, p. 6803, Sep 2023.
[60] A. K. Kuno, N. Begna, and F. Mebratu, "A feasibility analysis of PV-based off-grid rural electrification for a pastoral settlement in Ethiopia," Energy, vol. 282, p. 128899, Nov 2023. [ Links ]
[61] E. Y. Asuamah, S. Gyamfi, and A. Dagoumas, "Potential of meeting electricity needs of off-grid community with mini-grid solar systems," Scientific African, vol. 11, p. e00675, Mar 2021. doi: 10.1016/j.sciaf.2020.e00675. [ Links ]
This work was supported by the African Center of Excellence in Energy for Sustainable Development at the University of Rwanda.
* Corresponding author
Aban Ayik (S'18, M'22) received her B.S. degree in mechanical engineering in 1994 and her M.S. degree in electrical power engineering in 2009, both from the University of Khartoum, Khartoum, Sudan.
She previously worked for several years as a Mechanical Engineer with Sudan Sea Ports Corporation, where she gained experience in technical planning, capital equipment procurement, spare parts management, and project management. She later lectured at the School of Engineering at the University of Juba, South Sudan. She is currently a Ph.D. candidate with the African Center of Excellence in Energy for Sustainable Development (ACEESD), University of Rwanda, Kigali, Rwanda. Her research interests include assessing, modeling, and optimizing renewable energy systems, and energy storage technologies.
Aban is a registered Consultant Engineer with the Engineering Council of South Sudan, a Diploma Member of the Chartered Institute of Procurement & Supply (CIPS), and a Member of the African Network for Solar Energy (ANSOLE).
Nelson Ijumba (M'93, SM'17) graduated from the University of Dar es Salaam (Tanzania), and obtained his M.S and Ph.D. degrees from the Universities of Salford and Strathclyde (United Kingdom), respectively.
He is Emeritus Professor of Electrical Engineering at the University of Rwanda, based in the African Centre of Excellence in Energy for Sustainable Development (ACEESD), and also an Honorary Professor of Electrical Engineering, at the University of KwaZulu Natal, South Africa. He has over 40 years of experience in teaching, research, consulting and academic leadership. His research and consultancy services are in green energy, renewable energy resources exploitation, energy efficiency, electrical power systems, high voltage technology, innovation, higher education management and engineering education. He has published widely in indexed journals and made numerous presentations at international and local conferences. Prof Ijumba is passionate about the impact of technologies on sustainable development and translation of research outputs into socially relevant innovative products. He is currently the International Research and Innovation Programme Manager, based in the Africa Hub of Coventry University.
Prof Ijumba is a Fellow of the Southern African Institution of Electrical Engineers, a Member of the Academy of Sciences of South Africa, and Associate of Paeradigms and a Fellow of the South African Academy of Engineering. He is a registered Professional Engineer with the Engineering Council of South Africa and the Engineering Registration Board of Tanzania.
Charles Kabiri received his B.S. degree in electrical and electronics engineering from the National University of Rwanda in 2006, and his M.S. degree in information and communication systems in 2010 from Huazhong University of Science and Technology, Wuhan, China. He obtained his Ph.D. degree in telecommunication systems in April 2015 from Blekinge Institute of Technology, Faculty of Computing, Karlskrona, Sweden.
He worked at CIMERWA Ltd as an Eelectrical and Maintenance Engineer since 2007, before joining the Faculty of Applied Sciences at the National University of Rwanda in August 2007. He is currently serving as an Associate Professor at the College of Science and Technology, University of Rwanda, Rwanda. His research interests are in the areas of radio communications and renewable energies.
Philippe Goffin received his B.S. and M.S. degrees in mechanical engineering from ETH Zurich, Switzerland, in 2007 and 2009, respectively, and his Ph.D. degree in 2014, also from ETH Zurich.
He worked as a research assistant at the Chair of Building Systems under Professor HJ Leibundgut, from 2009 and 2014. His research focused on the development of control systems for low exergy building systems, particularly the interaction of ground-source heat pumps, ventilation, and low temperature radiant heating systems. Since 2015, he has been actively involved in the industry, working on and developing concepts for emission-free buildings and concepts for decarbonization of the industry in Switzerland (net-zero emissions by 2050).